(Reference Quantity : Full Range Deflection = FRD)
Ranges
|
•0-10 ppm Propane
•0-100 ppm Propane
•0-1.000 ppm Propane
•0-10.000 ppm Propane
•0-100.000 ppm Propane
|
Linearity
|
+/- 2 % FRD (up to Range 4)
|
Oxygen Cross Sensitivity
|
< +/- 2 % FRD
|
Availability
|
> 95 %
|
Limit of Detection
|
< 2 % FRD
|
Zero Drift
|
< 2 % FRD/week
|
Span Drift
|
< 4 % FRD/week
|
Response Time
|
approx. 1-2 s
|
Sample Flow Rate
|
approx. 220 l/h
|
Signal Output
|
0-10 V or 0/4-20 mA
|
Status Contacts
|
•Pre (Concentration-) Alarm
•Main (Concentration-) Alarm
•Range Identification
•Flame Out Indication
•Status Identification (Zero-Gas/Span- Gas/Calibration)
•Alarms (Pressure, Temperature, Flame)
|
Dimensions
|
19" x 267 x 500 mm (WxHxD)
|
Weight
|
approx. 26,5 kg
|
Ambient Temperature
|
+ 5 ... + 35 °C
|
Main Power
|
230 V / 50 Hz or 115 V / 60(50) Hz / 800 Watts
|